MANDÍK Tools is an app for Android phones and tablets and for Windows computers for operating and servicing MANDÍK air handling units. It combines two tools:
The app requires no login. Both tools are opened from the home page.
The Android app is free on Google Play – search for "MANDÍK Tools". The Windows version has the same functions and is always released in the same version.
| Android | Windows | |
|---|---|---|
| System | Android 8.0 or later | Windows 10 or 11, 64-bit |
| CLIMAN HMI | phone connected via WiFi to the unit's network (the network does not need internet access) | computer in the unit's network (cable or WiFi) |
| MANDÍK Modbus | RS485 – USB converter (phone with USB OTG support) | RS485 – USB converter (COM serial port) |
Connect the phone or computer to the same network as the air handling unit. Units are added in the Add unit section, which has three options. Tap an option's name to expand it; the ⓘ icon on the left shows its description.
| Option | Use |
|---|---|
| Current network | Shows the address range of the network the device is connected to (a computer with several networks shows each on its own line). Scan network searches it. |
| Address range | The unit is in a different address range, e.g. behind a router. Enter the range and tap Scan range (up to 10,000 addresses). |
| Enter IP address | Adds a unit by its known IP address without searching the network, button Add. The default address of a unit is 192.168.133.101. |
Units found are listed below the options. The + icon saves a unit, Save all saves all units found. Saved units are in the Saved devices list as AHU_1, AHU_2… The coloured dot next to a unit shows its state:
| Dot | State |
|---|---|
| green | the unit is reachable |
| red | the unit is not reachable |
| grey | the state is being checked |
The bin icon removes the unit from the list.
Tapping a unit in the list opens its details:
Units with an older version of the web interface do not send the unit information – the details keep showing "Information unavailable". The visualisation works for them as well.
The unit's visualisation opens full screen – it is the same page as in a browser at http://<unit IP>/hmi. The screen stays on while it is displayed. The Back button goes back through the pages of the visualisation and from the first page back to the app.
On Windows the visualisation opens in the default web browser.
Connect the RS485 – USB converter to the phone with a USB OTG cable. On the first connection Android asks for permission to access the device. Converters with FTDI, CP210x, CH34x, PL2303 and CDC-ACM chips are supported.
On Windows, plug the converter into a USB port; the app finds it as a serial (COM) port.
Then choose the device address, speed and parity (default 19200 Bd, 8E1) and tap Connect.
The scan finds the devices on the bus and recognises their type. The device type and the address range (From – To) can be limited. The app keeps communication quality statistics for every address.
| Device | Use | What the tool does |
|---|---|---|
| Honeywell / Resideo S4965 | burner controller (Monzun) | state, faults, remote reset, heating control |
| Climan EK IO module | Monzun-HPB | state, control, module profile, watchdog, board lock; from firmware 0424 the board's communication settings and DIP switch state |
| Midea AHU Application Kit | Monzun-HPA heat pump | state of the indoor and outdoor unit, control of operation, mode, fan speed and setpoint, Modbus address change |
| AMiT AMR-OP30ARH | temperature and humidity sensor | values, measurement corrections, Modbus address change |
| ebm-papst and Ziehl-Abegg ECblue EC fans | fans | operating values, faults and warnings, change of address, speed and parity |
| Copeland PEC100 and CAREL EVD evolution | heat pump circuit controllers | operating values, alarms, Modbus address change |
Every write (address, settings, commands) is protected by the Allow writing switch. Without it the tool only reads. When you leave the tool, the connected device is disconnected and the line is closed.
Commands written to the outputs of a Climan EK module are not reset when switching to another device or disconnecting – several outputs can stay switched on during a test. While the line is open, the app keeps reading the module and the commands stay active. After the line is closed, the module switches them off itself once its watchdog expires. The Monzun-HPA heat pump is not switched off when you leave the tool – switch it off manually. Monzun burner heating is switched off on disconnect.
Writing changes the settings of devices on the bus. The tool is intended for service technicians – before changing the address or communication settings, make sure the new settings match the control system.
The app does not collect or send any personal data and communicates only with devices on the local network or on the bus. See the privacy policy for details.
The version number is shown at the bottom of the app's home page. An overview of the versions and their changes is on the page MANDÍK Tools – app versions.