Supplement to the Modbus table. The list of alarm numbers is
too long to fit into the register table.
Numbers not listed should not appear. If one does, the unit runs a newer application version
than this document was written for.
Register 108 reports the number of the newest alarm still active (0 = none); when it clears, the next
active alarm takes over. Register 102 only says that an alarm of priority A to D is active, and the
acknowledgement is written to register 90. The full history with the times an alarm appeared and cleared is
available on the unit's web server – this list translates the number into its meaning.
Numbers are assigned in blocks by built-in component and are not contiguous; unused numbers are reserved
for future alarms.
| Code | Description |
|---|---|
| 1 | Damper 1 - Not open |
| 2 | Damper 2 - Not open |
| 3 | Damper 3 - Not open |
| 4 | Damper 4 - Not open |
| 5 | Damper 1 - Not closed |
| 6 | Damper 2 - Not closed |
| 7 | Damper 3 - Not closed |
| 8 | Damper 4 - Not closed |
| 9 | Room temperature 2 - Not connected |
| 10 | Room temperature 2 - Short circuit |
| 11 | Room temperature 3 - Not connected |
| 12 | Room temperature 3 - Short circuit |
| 13 | Room temperature 4 - Not connected |
| 14 | Room temperature 4 - Short circuit |
| 15 | BMS communication lost |
| 20 | Communication Error - Extension 1 |
| 21 | Communication Error - Extension 2 |
| 22 | Communication Error - Extension 3 |
| 23 | Communication Error - Extension 4 |
| 24 | Communication error - Room device |
| 25 | EPS - Fire alarm |
| 26 | Smoke sensor 1 |
| 27 | Smoke sensor 2 |
| 28 | Monitoring voltage relay |
| 29 | Recuperator pressure switch - Icing |
| 30 | Low supply air temperature |
| 31 | High supply air temperature |
| 32 | Heat recovery exchanger - Fault |
| 33 | Supply fan – fault |
| 34 | Exhaust fan – fault |
| 35 | Supply fan – communication fault |
| 36 | Exhaust fan – communication fault |
| 37 | Fan 1 failure - supply |
| 38 | Fan 1 failure - exhaust |
| 39 | Fan 2 failure - supply |
| 40 | Fan 2 failure - exhaust |
| 41 | Fan 3 failure - supply |
| 42 | Fan 3 failure - exhaust |
| 43 | Fan operation 1 - supply |
| 44 | Fan operation 1 - exhaust |
| 45 | Fan operation 2 - supply |
| 46 | Fan operation 2 - exhaust |
| 47 | Fan operation 3 - supply |
| 48 | Fan operation 3 - exhaust |
| 49 | Auxiliary contact of the power switch 1 - supply |
| 50 | Auxiliary contact of the power switch 1 - exhaust |
| 51 | Auxiliary contact of the power switch 2 - supply |
| 52 | Auxiliary contact of the power switch 2 - exhaust |
| 53 | Auxiliary contact of the power switch 3 - supply |
| 54 | Auxiliary contact of the power switch 3 - exhaust |
| 55 | Fan manostat - supply |
| 56 | Fan manostat - exhaust |
| 57 | High pressure - Circuit 1 |
| 58 | High pressure - Circuit 2 |
| 59 | Low pressure - Circuit 1 |
| 60 | Low pressure - Circuit 2 |
| 61 | Axial fan failure - Circuit 1 |
| 62 | Axial fan failure - Circuit 2 |
| 63 | Compressor discharge oil temperature - Circuit 1 |
| 64 | Compressor discharge oil temperature - Circuit 2 |
| 65 | Compressor temperature protection - Circuit 1 |
| 66 | Compressor temperature protection - Circuit 2 |
| 67 | Emerson Fault - Circuit 1 |
| 68 | Emerson Fault - Circuit 2 |
| 80 | Dirty supply filter 1 - 1st stage |
| 81 | Dirty supply filter 2 - 1st stage |
| 82 | Dirty supply filter 3 - 1st stage |
| 83 | Dirty exhaust filter 1 - 1st stage |
| 84 | Dirty exhaust filter 2 - 1st stage |
| 85 | Dirty exhaust filter 3 - 1st stage |
| 86 | Clogged supply filter 1 - 1st stage |
| 87 | Clogged supply filter 2 - 1st stage |
| 88 | Clogged supply filter 3 - 1st stage |
| 89 | Clogged exhaust filter 1 - 1st stage |
| 90 | Clogged exhaust filter 2 - 1st stage |
| 91 | Clogged exhaust filter 3 - 1st stage |
| 92 | Dirty supply filter 1 - 2nd stage |
| 93 | Dirty supply filter 2 - 2nd stage |
| 94 | Dirty supply filter 3 - 2nd stage |
| 95 | Dirty exhaust filter 1 - 2nd stage |
| 96 | Dirty exhaust filter 2 - 2nd stage |
| 97 | Dirty exhaust filter 3 - 2nd stage |
| 98 | Clogged supply filter 1 - 2nd stage |
| 99 | Clogged supply filter 2 - 2nd stage |
| 100 | Clogged supply filter 3 - 2nd stage |
| 101 | Clogged exhaust filter 1 - 2nd stage |
| 102 | Clogged exhaust filter 2 - 2nd stage |
| 103 | Clogged exhaust filter 3 - 2nd stage |
| 111 | Electric heater 1 fault - SSR 1 |
| 112 | Electric heater 1 fault - SSR 2 |
| 113 | Electric heater 1 fault - SSR 3 |
| 114 | Electric heater 1 fault - SSR 4 |
| 115 | Electric heater 1 fault - SSR 5 |
| 116 | Electric heater 1 fault - SSR 6 |
| 117 | Electric heater 1 fault - SSR 7 |
| 118 | Electric heater 1 fault - SSR 8 |
| 119 | Electric heater 1 fault - SSR 9 |
| 120 | Electric heater 1 fault - SSR 10 |
| 121 | Electric heater 2 fault - SSR 1 |
| 122 | Electric heater 2 fault - SSR 2 |
| 123 | Electric heater 2 fault - SSR 3 |
| 124 | Electric heater 2 fault - SSR 4 |
| 125 | Electric heater 2 fault - SSR 5 |
| 126 | Electric heater 2 fault - SSR 6 |
| 127 | Electric heater 2 fault - SSR 7 |
| 128 | Electric heater 2 fault - SSR 8 |
| 129 | Electric heater 2 fault - SSR 9 |
| 130 | Electric heater 2 fault - SSR 10 |
| 131 | Electric heater 3 fault - SSR 1 |
| 132 | Electric heater 3 fault - SSR 2 |
| 133 | Electric heater 3 fault - SSR 3 |
| 134 | Electric heater 3 fault - SSR 4 |
| 135 | Electric heater 3 fault - SSR 5 |
| 136 | Electric heater 3 fault - SSR 6 |
| 137 | Electric heater 3 fault - SSR 7 |
| 138 | Electric heater 3 fault - SSR 8 |
| 139 | Electric heater 3 fault - SSR 9 |
| 140 | Electric heater 3 fault - SSR 10 |
| 141 | Electric heater 1 - Safety thermostat |
| 142 | Electric heater 2 - Safety thermostat |
| 143 | Electric heater 3 - Safety thermostat |
| 144 | Electric heater 1 - Operating thermostat |
| 145 | Electric heater 2 - Operating thermostat |
| 146 | Electric heater 3 - Operating thermostat |
| 150 | Outdoor temperature - Not connected |
| 151 | Outdoor temperature - Short circuit |
| 152 | Inlet temperature - Not connected |
| 153 | Inlet temperature - Short circuit |
| 154 | Supply air temperature - Not connected |
| 155 | Supply air temperature - Short circuit |
| 156 | Extract air temperature - Not connected |
| 157 | Extract air temperature - Short circuit |
| 158 | Room temperature 1 - Not connected |
| 159 | Room temperature 1 - Short circuit |
| 160 | Exhaust air temperature - Not connected |
| 161 | Exhaust air temperature - Short circuit |
| 163 | Water exchanger 1 - Exchanger inlet temperature - Not connected |
| 164 | Water exchanger 2 - Exchanger inlet temperature - Not connected |
| 165 | Water exchanger 3 - Exchanger inlet temperature - Not connected |
| 166 | Water exchanger 4 - Exchanger inlet temperature - Not connected |
| 167 | Water exchanger 1 - Exchanger inlet temperature - Short circuit |
| 168 | Water exchanger 2 - Exchanger inlet temperature - Short circuit |
| 169 | Water exchanger 3 - Exchanger inlet temperature - Short circuit |
| 170 | Water exchanger 4 - Exchanger inlet temperature - Short circuit |
| 171 | Water exchanger 1 - Capillary thermostat |
| 172 | Water exchanger 2 - Capillary thermostat |
| 173 | Water exchanger 3 - Capillary thermostat |
| 174 | Water exchanger 4 - Capillary thermostat |
| 175 | Water exchanger 1 - Pump fault |
| 176 | Water exchanger 2 - Pump fault |
| 177 | Water exchanger 3 - Pump fault |
| 178 | Water exchanger 4 - Pump fault |
| 179 | Water exchanger 1 - Pump operation |
| 180 | Water exchanger 2 - Pump operation |
| 181 | Water exchanger 3 - Pump operation |
| 182 | Water exchanger 4 - Pump operation |
| 183 | Water exchanger 1 - Low water temperature |
| 184 | Water exchanger 2 - Low water temperature |
| 185 | Water exchanger 3 - Low water temperature |
| 186 | Water exchanger 4 - Low water temperature |
| 191 | Condensing unit 1 fault - Circuit 1 |
| 192 | Condensing unit 1 fault - Circuit 2 |
| 193 | Condensing unit 1 fault - Circuit 3 |
| 194 | Condensing unit 1 fault - Circuit 4 |
| 195 | Condensing unit 1 fault - Circuit 5 |
| 196 | Condensing unit 1 fault - Circuit 6 |
| 197 | Condensing unit 2 fault - Circuit 1 |
| 198 | Condensing unit 2 fault - Circuit 2 |
| 199 | Condensing unit 2 fault - Circuit 3 |
| 200 | Condensing unit 2 fault - Circuit 4 |
| 201 | Condensing unit 2 fault - Circuit 5 |
| 202 | Condensing unit 2 fault - Circuit 6 |
| 203 | Condensing unit 3 fault - Circuit 1 |
| 204 | Condensing unit 3 fault - Circuit 2 |
| 205 | Condensing unit 3 fault - Circuit 3 |
| 206 | Condensing unit 3 fault - Circuit 4 |
| 207 | Condensing unit 3 fault - Circuit 5 |
| 208 | Condensing unit 3 fault - Circuit 6 |
| 209 | Condensing unit 1 operation - Circuit 1 |
| 210 | Condensing unit 1 operation - Circuit 2 |
| 211 | Condensing unit 1 operation - Circuit 3 |
| 212 | Condensing unit 1 operation - Circuit 4 |
| 213 | Condensing unit 1 operation - Circuit 5 |
| 214 | Condensing unit 1 operation - Circuit 6 |
| 215 | Condensing unit 2 operation - Circuit 1 |
| 216 | Condensing unit 2 operation - Circuit 2 |
| 217 | Condensing unit 2 operation - Circuit 3 |
| 218 | Condensing unit 2 operation - Circuit 4 |
| 219 | Condensing unit 2 operation - Circuit 5 |
| 220 | Condensing unit 2 operation - Circuit 6 |
| 221 | Condensing unit 3 operation - Circuit 1 |
| 222 | Condensing unit 3 operation - Circuit 2 |
| 223 | Condensing unit 3 operation - Circuit 3 |
| 224 | Condensing unit 3 operation - Circuit 4 |
| 225 | Condensing unit 3 operation - Circuit 5 |
| 226 | Condensing unit 3 operation - Circuit 6 |
| 227 | Recuperator supply - Inlet temperature - Not connected |
| 228 | Recuperator supply - Inlet temperature - Short circuit |
| 229 | Recuperator supply - Outlet temperature - Not connected |
| 230 | Recuperator supply - Outlet temperature - Short circuit |
| 231 | Recuperator extract - Inlet temperature - Not connected |
| 232 | Recuperator extract - Inlet temperature - Short circuit |
| 233 | Recuperator extract - Outlet temperature - Not connected |
| 234 | Recuperator extract - Outlet temperature - Short circuit |
| 235 | Water exchanger 1 - Exchanger outlet temperature - Not connected |
| 236 | Water exchanger 2 - Exchanger outlet temperature - Not connected |
| 237 | Water exchanger 3 - Exchanger outlet temperature - Not connected |
| 238 | Water exchanger 4 - Exchanger outlet temperature - Not connected |
| 239 | Water exchanger 1 - Exchanger outlet temperature - Short circuit |
| 240 | Water exchanger 2 - Exchanger outlet temperature - Short circuit |
| 241 | Water exchanger 3 - Exchanger outlet temperature - Short circuit |
| 242 | Water exchanger 4 - Exchanger outlet temperature - Short circuit |
| 247 | Heat pump 2 - Compressor 2 discharge temperature (T6.2) |
| 248 | Heat pump 2 - Outdoor heat exchanger temperature (T7.2) |
| 249 | Heat pump 1 - Compressor 2 discharge temperature (T6.1) |
| 250 | Heat pump 1 - Outdoor heat exchanger temperature (T7.1) |
| 251 | Heat pump 1 - Low Press Mod |
| 252 | Heat pump 1 - Low Superheat Mod |
| 253 | Heat pump 1 - High Superheat Mod |
| 254 | Heat pump 1 - Refrigerant Loss Mod |
| 255 | Heat pump 1 - High Cond Press Mod |
| 256 | Heat pump 1 - Envelope Tc Low Mod |
| 257 | Heat pump 1 - Envelope Tc High Mod |
| 258 | Heat pump 1 - Envelope Te Low Mod |
| 259 | Heat pump 1 - Envelope Te High Mod |
| 260 | Heat pump 1 - Freeze Alarm Mod |
| 261 | Heat pump 1 - Envelope Alarm Mod |
| 262 | Heat pump 1 - Defrost Term Overtime Mod |
| 263 | Heat pump 1 - Compressor1 High Discharge Temp Mod |
| 264 | Heat pump 1 - 4Valve Ins Press Dif Mod |
| 265 | Heat pump 1 - Low pressure (P1.1) |
| 266 | Heat pump 1 - High pressure (P2.1) |
| 267 | Heat pump 1 - Outdoor coil vapor temperature (T1.1) |
| 268 | Heat pump 1 - Compressor suction temperature (T2.1) |
| 269 | Heat pump 1 - Air temperature before outdoor heat exchanger (T3.1) |
| 270 | Heat pump 1 - Temperature before expansion valve (T4.1) |
| 271 | Heat pump 1 - Compressor 1 discharge temperature (T5.1) |
| 272 | Heat pump 1 - VSDrive Comm Mod |
| 273 | Heat pump 1 - EEPROM Mod |
| 274 | Heat pump 1 - Comm Timeout Mod |
| 275 | Heat pump 1 - VSDrive Alarm Mod |
| 276 | Heat pump 1 - VSDrive Config Mod |
| 277 | Heat pump 1 - Circuit1 FB safety Mod |
| 278 | Heat pump 1 - System Power Loss Mod |
| 279 | Heat pump 1 - VSDrive Locked Mod |
| 280 | Heat pump 1 - Valve Config Mod |
| 281 | Heat pump 1 - Valve1 Mod |
| 282 | Heat pump 1 - VSDrive Startup Mod |
| 283 | Heat pump 1 - Pack Config Mod |
| 284 | Heat pump 1 - Config Status Mod |
| 285 | Heat pump 1 - Speed Foldback Mod |
| 286 | Heat pump 1 - PFC Temp Foldback Mod |
| 287 | Heat pump 1 - ACline Current Foldback Mod |
| 288 | Heat pump 1 - Compressor Phase Current Mod |
| 289 | Heat pump 1 - Compressor Power Module Temp Mod |
| 290 | Heat pump 1 - DLT Temp Mod |
| 291 | Heat pump 1 - Envelope Mod |
| 292 | Heat pump 1 - Autosaved Data Mod |
| 293 | Heat pump 1 - Torque limit Mod |
| 294 | Heat pump 1 - Ambient Temp Mod |
| 295 | Heat pump 1 - Outside Compressor Envelope Mod |
| 296 | Heat pump 2 - Low Press Mod |
| 297 | Heat pump 2 - Low Superheat Mod |
| 298 | Heat pump 2 - High Superheat Mod |
| 299 | Heat pump 2 - Refrigerant Loss Mod |
| 300 | Heat pump 2 - High Cond Press Mod |
| 301 | Heat pump 2 - Envelope Tc Low Mod |
| 302 | Heat pump 2 - Envelope Tc High Mod |
| 303 | Heat pump 2 - Envelope Te Low Mod |
| 304 | Heat pump 2 - Envelope Te High Mod |
| 305 | Heat pump 2 - Freeze Alarm Mod |
| 306 | Heat pump 2 - Envelope Alarm Mod |
| 307 | Heat pump 2 - Defrost Term Overtime Mod |
| 308 | Heat pump 2 - Compressor1 High Discharge Temp Mod |
| 309 | Heat pump 2 - 4Valve Ins Press Dif Mod |
| 310 | Heat pump 2 - Low pressure (P1.2) |
| 311 | Heat pump 2 - High pressure (P2.2) |
| 312 | Heat pump 2 - Outdoor coil vapor temperature (T1.2) |
| 313 | Heat pump 2 - Compressor suction temperature (T2.2) |
| 314 | Heat pump 2 - Air temperature before outdoor heat exchanger (T3.2) |
| 315 | Heat pump 2 - Temperature before expansion valve (T4.2) |
| 316 | Heat pump 2 - Compressor 1 discharge temperature (T5.2) |
| 317 | Heat pump 2 - VSDrive Comm Mod |
| 318 | Heat pump 2 - EEPROM Mod |
| 319 | Heat pump 2 - Comm Timeout Mod |
| 320 | Heat pump 2 - VSDrive Alarm Mod |
| 321 | Heat pump 2 - VSDrive Config Mod |
| 322 | Heat pump 2 - Circuit1 FB safety Mod |
| 323 | Heat pump 2 - System Power Loss Mod |
| 324 | Heat pump 2 - VSDrive Locked Mod |
| 325 | Heat pump 2 - Valve Config Mod |
| 326 | Heat pump 2 - Valve1 Mod |
| 327 | Heat pump 2 - VSDrive Startup Mod |
| 328 | Heat pump 2 - Pack Config Mod |
| 329 | Heat pump 2 - Config Status Mod |
| 330 | Heat pump 2 - Speed Foldback Mod |
| 331 | Heat pump 2 - PFC Temp Foldback Mod |
| 332 | Heat pump 2 - ACline Current Foldback Mod |
| 333 | Heat pump 2 - Compressor Phase Current Mod |
| 334 | Heat pump 2 - Compressor Power Module Temp Mod |
| 335 | Heat pump 2 - DLT Temp Mod |
| 336 | Heat pump 2 - Envelope Mod |
| 337 | Heat pump 2 - Autosaved Data Mod |
| 338 | Heat pump 2 - Torque limit Mod |
| 339 | Heat pump 2 - Ambient Temp Mod |
| 340 | Heat pump 2 - Outside Compressor Envelope Mod |
| 350 | Recuperator: exchanger fouling — defrost did not return the pressure drop to normal, clean the exchanger |