Long state enumerations (managers, fan control reason, condensing unit and electric heater sections, compressor) are on the page Register states,
alarm numbers on the page Alarm numbers. Register 102 reports that an alarm of priority A to D is active,
register 108 the number of the current alarm.
The table is generic, it contains all registers. For a specific unit, download the export in the visualization on the Network page, section BMS (Modbus, BACnet).
| Registers | Contents |
|---|---|
| 1–69 | Write – mode selection, temperature and fan setpoints per mode |
| 70–89 | Write – humidity and CO₂ setpoints per mode, room sensor values from BMS |
| 90–99 | Write – commands |
| 100–149 | Unit state, alarm, managers |
| 150–199 | Sensors |
| 200–249 | Fans |
| 250–299 | Dampers, mixing damper, heat recovery |
| 300–349 | Water heating / cooling |
| 350–449 | Condensing units |
| 450–599 | Electric heaters |
| 600–649 | Integrated heat pumps |
| 650–699 | Filters |
A single request may only cover registers from one row of this table. Ranges are given as register numbers; subtract 1 for the address.
| Function | Contiguous ranges |
|---|---|
| Holding registers (3, 6, 16) | 1–92 |
| Input registers (4) | 100–109, 150–169, 200–205, 210–215, 250–261, 300–315, 350–424, 450–572, 600–623, 650–673 |
| Register address | Register number | Function | Data type | Unit | Meaning / value range | Description |
|---|---|---|---|---|---|---|
| 0 | 1 | HoldingRegister | U16 | 0 = Off 1 = Mode 1 2 = Mode 2 3 = Mode 3 4 = Mode 4 5 = Weekly schedule |
Mode selection | |
| 1 | 2 | HoldingRegister | U16 | °C × 10 | 0–500 (= 0.0–50.0 °C) | Temperature setpoint - Mode 1 |
| 2 | 3 | HoldingRegister | U16 | °C × 10 | 0–500 (= 0.0–50.0 °C) | Temperature setpoint - Mode 2 |
| 3 | 4 | HoldingRegister | U16 | °C × 10 | 0–500 (= 0.0–50.0 °C) | Temperature setpoint - Mode 3 |
| 4 | 5 | HoldingRegister | U16 | °C × 10 | 0–500 (= 0.0–50.0 °C) | Temperature setpoint - Mode 4 |
| 5 | 6 | HoldingRegister | U16 | % | 0-100 | Supply air setpoint - speed - Mode 1 |
| 6 | 7 | HoldingRegister | U16 | % | 0-100 | Supply air setpoint - speed - Mode 2 |
| 7 | 8 | HoldingRegister | U16 | % | 0-100 | Supply air setpoint - speed - Mode 3 |
| 8 | 9 | HoldingRegister | U16 | % | 0-100 | Supply air setpoint - speed - Mode 4 |
| 9 | 10 | HoldingRegister | U16 | % | 0-100 | Supply air maximum - speed - Mode 1 |
| 10 | 11 | HoldingRegister | U16 | % | 0-100 | Supply air maximum - speed - Mode 2 |
| 11 | 12 | HoldingRegister | U16 | % | 0-100 | Supply air maximum - speed - Mode 3 |
| 12 | 13 | HoldingRegister | U16 | % | 0-100 | Supply air maximum - speed - Mode 4 |
| 13 | 14 | HoldingRegister | U16 | % | 0-100 | Extract air setpoint - speed - Mode 1 |
| 14 | 15 | HoldingRegister | U16 | % | 0-100 | Extract air setpoint - speed - Mode 2 |
| 15 | 16 | HoldingRegister | U16 | % | 0-100 | Extract air setpoint - speed - Mode 3 |
| 16 | 17 | HoldingRegister | U16 | % | 0-100 | Extract air setpoint - speed - Mode 4 |
| 17 | 18 | HoldingRegister | U16 | % | 0-100 | Extract air maximum - speed - Mode 1 |
| 18 | 19 | HoldingRegister | U16 | % | 0-100 | Extract air maximum - speed - Mode 2 |
| 19 | 20 | HoldingRegister | U16 | % | 0-100 | Extract air maximum - speed - Mode 3 |
| 20 | 21 | HoldingRegister | U16 | % | 0-100 | Extract air maximum - speed - Mode 4 |
| 21 | 22 | HoldingRegister | U16 | Pa | Supply air setpoint - pressure - Mode 1 | |
| 22 | 23 | HoldingRegister | U16 | Pa | Supply air setpoint - pressure - Mode 2 | |
| 23 | 24 | HoldingRegister | U16 | Pa | Supply air setpoint - pressure - Mode 3 | |
| 24 | 25 | HoldingRegister | U16 | Pa | Supply air setpoint - pressure - Mode 4 | |
| 25 | 26 | HoldingRegister | U16 | Pa | Supply air maximum - pressure - Mode 1 | |
| 26 | 27 | HoldingRegister | U16 | Pa | Supply air maximum - pressure - Mode 2 | |
| 27 | 28 | HoldingRegister | U16 | Pa | Supply air maximum - pressure - Mode 3 | |
| 28 | 29 | HoldingRegister | U16 | Pa | Supply air maximum - pressure - Mode 4 | |
| 29 | 30 | HoldingRegister | U16 | Pa | Extract air setpoint - pressure - Mode 1 | |
| 30 | 31 | HoldingRegister | U16 | Pa | Extract air setpoint - pressure - Mode 2 | |
| 31 | 32 | HoldingRegister | U16 | Pa | Extract air setpoint - pressure - Mode 3 | |
| 32 | 33 | HoldingRegister | U16 | Pa | Extract air setpoint - pressure - Mode 4 | |
| 33 | 34 | HoldingRegister | U16 | Pa | Extract air maximum - pressure - Mode 1 | |
| 34 | 35 | HoldingRegister | U16 | Pa | Extract air maximum - pressure - Mode 2 | |
| 35 | 36 | HoldingRegister | U16 | Pa | Extract air maximum - pressure - Mode 3 | |
| 36 | 37 | HoldingRegister | U16 | Pa | Extract air maximum - pressure - Mode 4 | |
| 37 | 38 | HoldingRegister | U32 | m³/h | Supply air setpoint - airflow - Mode 1 | |
| 39 | 40 | HoldingRegister | U32 | m³/h | Supply air setpoint - airflow - Mode 2 | |
| 41 | 42 | HoldingRegister | U32 | m³/h | Supply air setpoint - airflow - Mode 3 | |
| 43 | 44 | HoldingRegister | U32 | m³/h | Supply air setpoint - airflow - Mode 4 | |
| 45 | 46 | HoldingRegister | U32 | m³/h | Supply air maximum - airflow - Mode 1 | |
| 47 | 48 | HoldingRegister | U32 | m³/h | Supply air maximum - airflow - Mode 2 | |
| 49 | 50 | HoldingRegister | U32 | m³/h | Supply air maximum - airflow - Mode 3 | |
| 51 | 52 | HoldingRegister | U32 | m³/h | Supply air maximum - airflow - Mode 4 | |
| 53 | 54 | HoldingRegister | U32 | m³/h | Extract air setpoint - airflow - Mode 1 | |
| 55 | 56 | HoldingRegister | U32 | m³/h | Extract air setpoint - airflow - Mode 2 | |
| 57 | 58 | HoldingRegister | U32 | m³/h | Extract air setpoint - airflow - Mode 3 | |
| 59 | 60 | HoldingRegister | U32 | m³/h | Extract air setpoint - airflow - Mode 4 | |
| 61 | 62 | HoldingRegister | U32 | m³/h | Extract air maximum - airflow - Mode 1 | |
| 63 | 64 | HoldingRegister | U32 | m³/h | Extract air maximum - airflow - Mode 2 | |
| 65 | 66 | HoldingRegister | U32 | m³/h | Extract air maximum - airflow - Mode 3 | |
| 67 | 68 | HoldingRegister | U32 | m³/h | Extract air maximum - airflow - Mode 4 | |
| 69 | 70 | HoldingRegister | U16 | % | 0–100 | Relative humidity setpoint - Mode 1 |
| 70 | 71 | HoldingRegister | U16 | % | 0–100 | Relative humidity setpoint - Mode 2 |
| 71 | 72 | HoldingRegister | U16 | % | 0–100 | Relative humidity setpoint - Mode 3 |
| 72 | 73 | HoldingRegister | U16 | % | 0–100 | Relative humidity setpoint - Mode 4 |
| 73 | 74 | HoldingRegister | U16 | ppm | 0–2000 | CO₂ setpoint - Mode 1 |
| 74 | 75 | HoldingRegister | U16 | ppm | 0–2000 | CO₂ setpoint - Mode 2 |
| 75 | 76 | HoldingRegister | U16 | ppm | 0–2000 | CO₂ setpoint - Mode 3 |
| 76 | 77 | HoldingRegister | U16 | ppm | 0–2000 | CO₂ setpoint - Mode 4 |
| 77 | 78 | HoldingRegister | S16 | °C × 10 | Temperature from BMS – Room 1 (ROOM1) | |
| 78 | 79 | HoldingRegister | S16 | °C × 10 | Temperature from BMS – Room 2 (ROOM2) | |
| 79 | 80 | HoldingRegister | S16 | °C × 10 | Temperature from BMS – Room 3 (ROOM3) | |
| 80 | 81 | HoldingRegister | S16 | °C × 10 | Temperature from BMS – Room 4 (ROOM4) | |
| 81 | 82 | HoldingRegister | U16 | % | 0–100 | Humidity from BMS – Room 1 (ROOM1) |
| 82 | 83 | HoldingRegister | U16 | % | 0–100 | Humidity from BMS – Room 2 (ROOM2) |
| 83 | 84 | HoldingRegister | U16 | % | 0–100 | Humidity from BMS – Room 3 (ROOM3) |
| 84 | 85 | HoldingRegister | U16 | % | 0–100 | Humidity from BMS – Room 4 (ROOM4) |
| 85 | 86 | HoldingRegister | U16 | ppm | CO₂ from BMS – Room 1 (ROOM1) | |
| 86 | 87 | HoldingRegister | U16 | ppm | CO₂ from BMS – Room 2 (ROOM2) | |
| 87 | 88 | HoldingRegister | U16 | ppm | CO₂ from BMS – Room 3 (ROOM3) | |
| 88 | 89 | HoldingRegister | U16 | ppm | CO₂ from BMS – Room 4 (ROOM4) | |
| 89 | 90 | HoldingRegister | U16 | 1 = acknowledge alarms | Alarm reset. Pulse, the unit clears the register itself. Only with writes from the BMS enabled and a live heartbeat. The alarm state is in register 102, the current alarm number in register 108. | |
| 90 | 91 | HoldingRegister | U16 | write a value > 0 | BMS heartbeat (condition for writes). The BMS periodically writes a value greater than 0 here (e.g. 1); the unit keeps it for the set time and then resets it to 0, and if it stays zero for another set time the connection is lost. Without a live heartbeat writes from the BMS are not taken over and BMS-type sensors are treated as not connected; alarm 15 only when some sensor takes its value from the BMS. | |
| 91 | 92 | HoldingRegister | U16 | min | 1–60 | Heartbeat timeout. The same setting as on the Communication page; the BMS can set it itself. A value below 1 is taken as 1. |
| 99 | 100 | InputRegister | U16 | 0 = Off 1 = Mode 1 2 = Mode 2 3 = Mode 3 4 = Mode 4 |
Current mode | |
| 100 | 101 | InputRegister | U16 | see Register states | Temperature manager state | |
| 101 | 102 | InputRegister | U16 | 0 = OK 1 = Alarm |
Unit state. Tracks priority A to D alarms; priority E warnings are not reflected here. The alarm number is in register 108, the reset in register 90, list see Alarm numbers. | |
| 102 | 103 | InputRegister | U16 | 0 = running according to mode or weekly schedule 1 = switched off by a priority A or B alarm 2 = BMS contact open 3 = switched off by the room device |
Reason for unit shutdown | |
| 103 | 104 | InputRegister | U16 | see Register states | Humidity manager state | |
| 104 | 105 | InputRegister | U16 | 0 = Off 1 = PID control 2 = Ventilation at maximum 3 = Hysteresis - idle 4 = Boost ventilation 5 = Sensor missing |
CO₂ manager state | |
| 105 | 106 | InputRegister | S16 | °C × 10 | Temperature manager target temperature - mode setpoint after room device correction and summer shift | |
| 106 | 107 | InputRegister | S16 | °C × 10 | Supply air temperature setpoint | |
| 107 | 108 | InputRegister | U16 | 0 = no alarm | Current alarm number – the newest alarm still active, see Alarm numbers. When it clears, the next active alarm takes over. | |
| 108 | 109 | InputRegister | U16 | 0 = no connection 1 = connected |
Connection to the BMS according to the heartbeat (register 91). 1 also when the watchdog is off. | |
| 149 | 150 | InputRegister | S16 | °C × 10 | Temperature – Outdoor | |
| 150 | 151 | InputRegister | S16 | °C × 10 | Temperature – ODA (in the unit) | |
| 151 | 152 | InputRegister | S16 | °C × 10 | Temperature – Supply (SUP) | |
| 152 | 153 | InputRegister | U16 | % | Humidity – Supply (SUP) | |
| 153 | 154 | InputRegister | S16 | °C × 10 | Temperature – Room 1 (ROOM1) | |
| 154 | 155 | InputRegister | U16 | % | Humidity – Room 1 (ROOM1) | |
| 155 | 156 | InputRegister | U16 | ppm | CO₂ – Room 1 (ROOM1) | |
| 156 | 157 | InputRegister | S16 | °C × 10 | Temperature – Room 2 (ROOM2) | |
| 157 | 158 | InputRegister | U16 | % | Humidity – Room 2 (ROOM2) | |
| 158 | 159 | InputRegister | U16 | ppm | CO₂ – Room 2 (ROOM2) | |
| 159 | 160 | InputRegister | S16 | °C × 10 | Temperature – Room 3 (ROOM3) | |
| 160 | 161 | InputRegister | U16 | % | Humidity – Room 3 (ROOM3) | |
| 161 | 162 | InputRegister | U16 | ppm | CO₂ – Room 3 (ROOM3) | |
| 162 | 163 | InputRegister | S16 | °C × 10 | Temperature – Room 4 (ROOM4) | |
| 163 | 164 | InputRegister | U16 | % | Humidity – Room 4 (ROOM4) | |
| 164 | 165 | InputRegister | U16 | ppm | CO₂ – Room 4 (ROOM4) | |
| 165 | 166 | InputRegister | S16 | °C × 10 | Temperature – Extract (ETA) | |
| 166 | 167 | InputRegister | U16 | % | Humidity – Extract (ETA) | |
| 167 | 168 | InputRegister | U16 | ppm | CO₂ – Extract (ETA) | |
| 168 | 169 | InputRegister | S16 | °C × 10 | Temperature – Exhaust (EHA) | |
| 199 | 200 | InputRegister | U16 | 0 = Off 1 = Automatic state 2 = Manual control |
Supply fan state | |
| 200 | 201 | InputRegister | U16 | see Register states | Automatic state detail – Supply fan | |
| 201 | 202 | InputRegister | U16 | % | 0–100 | Speed – Supply fan |
| 202 | 203 | InputRegister | U16 | 0 = Off 1 = Running |
Running – Supply fan | |
| 203 | 204 | InputRegister | U16 | Pa | Differential pressure – Supply fan | |
| 204 | 205 | InputRegister | U16 | m³/h ÷ 10 | Airflow – Supply fan | |
| 209 | 210 | InputRegister | U16 | 0 = Off 1 = Automatic state 2 = Manual control |
Exhaust fan state | |
| 210 | 211 | InputRegister | U16 | see Register states | Automatic state detail – Exhaust fan | |
| 211 | 212 | InputRegister | U16 | % | 0–100 | Speed – Exhaust fan |
| 212 | 213 | InputRegister | U16 | 0 = Off 1 = Running |
Running – Exhaust fan | |
| 213 | 214 | InputRegister | U16 | Pa | Differential pressure – Exhaust fan | |
| 214 | 215 | InputRegister | U16 | m³/h ÷ 10 | Airflow – Exhaust fan | |
| 249 | 250 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Manual control |
State – Damper 1 | |
| 250 | 251 | InputRegister | U16 | % | 0–100 | Position – Damper 1 |
| 251 | 252 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Manual control |
State – Damper 2 | |
| 252 | 253 | InputRegister | U16 | % | 0–100 | Position – Damper 2 |
| 253 | 254 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Manual control |
State – Damper 3 | |
| 254 | 255 | InputRegister | U16 | % | 0–100 | Position – Damper 3 |
| 255 | 256 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Manual control |
State – Damper 4 | |
| 256 | 257 | InputRegister | U16 | % | 0–100 | Position – Damper 4 |
| 257 | 258 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Min 3 = Max 4 = Manual control |
State – Mixing damper | |
| 258 | 259 | InputRegister | U16 | % | 0–100 | Position – Mixing damper |
| 259 | 260 | InputRegister | U16 | 0 = Off 1 = Auto 2 = Max 3 = Manual control 4 = Frost |
State – Heat recovery | |
| 260 | 261 | InputRegister | U16 | % | 0–100 | Output – Heat recovery |
| 299 | 300 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Frost - capillary thermostat 5 = Water protection - control intervening |
State – Water heating/cooling 1 | |
| 300 | 301 | InputRegister | U16 | % | 0–100 | Output – Water heating/cooling 1 |
| 301 | 302 | InputRegister | U16 | h | Running hours – Water heating/cooling 1 | |
| 302 | 303 | InputRegister | U16 | Start count – Water heating/cooling 1 | ||
| 303 | 304 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Frost - capillary thermostat 5 = Water protection - control intervening |
State – Water heating/cooling 2 | |
| 304 | 305 | InputRegister | U16 | % | 0–100 | Output – Water heating/cooling 2 |
| 305 | 306 | InputRegister | U16 | h | Running hours – Water heating/cooling 2 | |
| 306 | 307 | InputRegister | U16 | Start count – Water heating/cooling 2 | ||
| 307 | 308 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Frost - capillary thermostat 5 = Water protection - control intervening |
State – Water heating/cooling 3 | |
| 308 | 309 | InputRegister | U16 | % | 0–100 | Output – Water heating/cooling 3 |
| 309 | 310 | InputRegister | U16 | h | Running hours – Water heating/cooling 3 | |
| 310 | 311 | InputRegister | U16 | Start count – Water heating/cooling 3 | ||
| 311 | 312 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Frost - capillary thermostat 5 = Water protection - control intervening |
State – Water heating/cooling 4 | |
| 312 | 313 | InputRegister | U16 | % | 0–100 | Output – Water heating/cooling 4 |
| 313 | 314 | InputRegister | U16 | h | Running hours – Water heating/cooling 4 | |
| 314 | 315 | InputRegister | U16 | Start count – Water heating/cooling 4 | ||
| 349 | 350 | InputRegister | U16 | % | 0–100 | Total output – Condensing unit 1 |
| 350 | 351 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 1 | |
| 351 | 352 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 1 |
| 352 | 353 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 1 | |
| 353 | 354 | InputRegister | U16 | Start count – Condensing unit 1, section 1 | ||
| 354 | 355 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 2 | |
| 355 | 356 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 2 |
| 356 | 357 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 2 | |
| 357 | 358 | InputRegister | U16 | Start count – Condensing unit 1, section 2 | ||
| 358 | 359 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 3 | |
| 359 | 360 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 3 |
| 360 | 361 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 3 | |
| 361 | 362 | InputRegister | U16 | Start count – Condensing unit 1, section 3 | ||
| 362 | 363 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 4 | |
| 363 | 364 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 4 |
| 364 | 365 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 4 | |
| 365 | 366 | InputRegister | U16 | Start count – Condensing unit 1, section 4 | ||
| 366 | 367 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 5 | |
| 367 | 368 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 5 |
| 368 | 369 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 5 | |
| 369 | 370 | InputRegister | U16 | Start count – Condensing unit 1, section 5 | ||
| 370 | 371 | InputRegister | U16 | see Register states | State – Condensing unit 1, section 6 | |
| 371 | 372 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 1, section 6 |
| 372 | 373 | InputRegister | U16 | h | Running hours – Condensing unit 1, section 6 | |
| 373 | 374 | InputRegister | U16 | Start count – Condensing unit 1, section 6 | ||
| 374 | 375 | InputRegister | U16 | % | 0–100 | Total output – Condensing unit 2 |
| 375 | 376 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 1 | |
| 376 | 377 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 1 |
| 377 | 378 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 1 | |
| 378 | 379 | InputRegister | U16 | Start count – Condensing unit 2, section 1 | ||
| 379 | 380 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 2 | |
| 380 | 381 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 2 |
| 381 | 382 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 2 | |
| 382 | 383 | InputRegister | U16 | Start count – Condensing unit 2, section 2 | ||
| 383 | 384 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 3 | |
| 384 | 385 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 3 |
| 385 | 386 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 3 | |
| 386 | 387 | InputRegister | U16 | Start count – Condensing unit 2, section 3 | ||
| 387 | 388 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 4 | |
| 388 | 389 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 4 |
| 389 | 390 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 4 | |
| 390 | 391 | InputRegister | U16 | Start count – Condensing unit 2, section 4 | ||
| 391 | 392 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 5 | |
| 392 | 393 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 5 |
| 393 | 394 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 5 | |
| 394 | 395 | InputRegister | U16 | Start count – Condensing unit 2, section 5 | ||
| 395 | 396 | InputRegister | U16 | see Register states | State – Condensing unit 2, section 6 | |
| 396 | 397 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 2, section 6 |
| 397 | 398 | InputRegister | U16 | h | Running hours – Condensing unit 2, section 6 | |
| 398 | 399 | InputRegister | U16 | Start count – Condensing unit 2, section 6 | ||
| 399 | 400 | InputRegister | U16 | % | 0–100 | Total output – Condensing unit 3 |
| 400 | 401 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 1 | |
| 401 | 402 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 1 |
| 402 | 403 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 1 | |
| 403 | 404 | InputRegister | U16 | Start count – Condensing unit 3, section 1 | ||
| 404 | 405 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 2 | |
| 405 | 406 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 2 |
| 406 | 407 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 2 | |
| 407 | 408 | InputRegister | U16 | Start count – Condensing unit 3, section 2 | ||
| 408 | 409 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 3 | |
| 409 | 410 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 3 |
| 410 | 411 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 3 | |
| 411 | 412 | InputRegister | U16 | Start count – Condensing unit 3, section 3 | ||
| 412 | 413 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 4 | |
| 413 | 414 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 4 |
| 414 | 415 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 4 | |
| 415 | 416 | InputRegister | U16 | Start count – Condensing unit 3, section 4 | ||
| 416 | 417 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 5 | |
| 417 | 418 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 5 |
| 418 | 419 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 5 | |
| 419 | 420 | InputRegister | U16 | Start count – Condensing unit 3, section 5 | ||
| 420 | 421 | InputRegister | U16 | see Register states | State – Condensing unit 3, section 6 | |
| 421 | 422 | InputRegister | U16 | % | 0–100 | Output – Condensing unit 3, section 6 |
| 422 | 423 | InputRegister | U16 | h | Running hours – Condensing unit 3, section 6 | |
| 423 | 424 | InputRegister | U16 | Start count – Condensing unit 3, section 6 | ||
| 449 | 450 | InputRegister | U16 | % | 0–100 | Total output – Electric heater 1 |
| 450 | 451 | InputRegister | U16 | see Register states | State – Electric heater 1, section 1 | |
| 451 | 452 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 1 |
| 452 | 453 | InputRegister | U16 | h | Running hours – Electric heater 1, section 1 | |
| 453 | 454 | InputRegister | U16 | Start count – Electric heater 1, section 1 | ||
| 454 | 455 | InputRegister | U16 | see Register states | State – Electric heater 1, section 2 | |
| 455 | 456 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 2 |
| 456 | 457 | InputRegister | U16 | h | Running hours – Electric heater 1, section 2 | |
| 457 | 458 | InputRegister | U16 | Start count – Electric heater 1, section 2 | ||
| 458 | 459 | InputRegister | U16 | see Register states | State – Electric heater 1, section 3 | |
| 459 | 460 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 3 |
| 460 | 461 | InputRegister | U16 | h | Running hours – Electric heater 1, section 3 | |
| 461 | 462 | InputRegister | U16 | Start count – Electric heater 1, section 3 | ||
| 462 | 463 | InputRegister | U16 | see Register states | State – Electric heater 1, section 4 | |
| 463 | 464 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 4 |
| 464 | 465 | InputRegister | U16 | h | Running hours – Electric heater 1, section 4 | |
| 465 | 466 | InputRegister | U16 | Start count – Electric heater 1, section 4 | ||
| 466 | 467 | InputRegister | U16 | see Register states | State – Electric heater 1, section 5 | |
| 467 | 468 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 5 |
| 468 | 469 | InputRegister | U16 | h | Running hours – Electric heater 1, section 5 | |
| 469 | 470 | InputRegister | U16 | Start count – Electric heater 1, section 5 | ||
| 470 | 471 | InputRegister | U16 | see Register states | State – Electric heater 1, section 6 | |
| 471 | 472 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 6 |
| 472 | 473 | InputRegister | U16 | h | Running hours – Electric heater 1, section 6 | |
| 473 | 474 | InputRegister | U16 | Start count – Electric heater 1, section 6 | ||
| 474 | 475 | InputRegister | U16 | see Register states | State – Electric heater 1, section 7 | |
| 475 | 476 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 7 |
| 476 | 477 | InputRegister | U16 | h | Running hours – Electric heater 1, section 7 | |
| 477 | 478 | InputRegister | U16 | Start count – Electric heater 1, section 7 | ||
| 478 | 479 | InputRegister | U16 | see Register states | State – Electric heater 1, section 8 | |
| 479 | 480 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 8 |
| 480 | 481 | InputRegister | U16 | h | Running hours – Electric heater 1, section 8 | |
| 481 | 482 | InputRegister | U16 | Start count – Electric heater 1, section 8 | ||
| 482 | 483 | InputRegister | U16 | see Register states | State – Electric heater 1, section 9 | |
| 483 | 484 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 9 |
| 484 | 485 | InputRegister | U16 | h | Running hours – Electric heater 1, section 9 | |
| 485 | 486 | InputRegister | U16 | Start count – Electric heater 1, section 9 | ||
| 486 | 487 | InputRegister | U16 | see Register states | State – Electric heater 1, section 10 | |
| 487 | 488 | InputRegister | U16 | % | 0–100 | Output – Electric heater 1, section 10 |
| 488 | 489 | InputRegister | U16 | h | Running hours – Electric heater 1, section 10 | |
| 489 | 490 | InputRegister | U16 | Start count – Electric heater 1, section 10 | ||
| 490 | 491 | InputRegister | U16 | % | 0–100 | Total output – Electric heater 2 |
| 491 | 492 | InputRegister | U16 | see Register states | State – Electric heater 2, section 1 | |
| 492 | 493 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 1 |
| 493 | 494 | InputRegister | U16 | h | Running hours – Electric heater 2, section 1 | |
| 494 | 495 | InputRegister | U16 | Start count – Electric heater 2, section 1 | ||
| 495 | 496 | InputRegister | U16 | see Register states | State – Electric heater 2, section 2 | |
| 496 | 497 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 2 |
| 497 | 498 | InputRegister | U16 | h | Running hours – Electric heater 2, section 2 | |
| 498 | 499 | InputRegister | U16 | Start count – Electric heater 2, section 2 | ||
| 499 | 500 | InputRegister | U16 | see Register states | State – Electric heater 2, section 3 | |
| 500 | 501 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 3 |
| 501 | 502 | InputRegister | U16 | h | Running hours – Electric heater 2, section 3 | |
| 502 | 503 | InputRegister | U16 | Start count – Electric heater 2, section 3 | ||
| 503 | 504 | InputRegister | U16 | see Register states | State – Electric heater 2, section 4 | |
| 504 | 505 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 4 |
| 505 | 506 | InputRegister | U16 | h | Running hours – Electric heater 2, section 4 | |
| 506 | 507 | InputRegister | U16 | Start count – Electric heater 2, section 4 | ||
| 507 | 508 | InputRegister | U16 | see Register states | State – Electric heater 2, section 5 | |
| 508 | 509 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 5 |
| 509 | 510 | InputRegister | U16 | h | Running hours – Electric heater 2, section 5 | |
| 510 | 511 | InputRegister | U16 | Start count – Electric heater 2, section 5 | ||
| 511 | 512 | InputRegister | U16 | see Register states | State – Electric heater 2, section 6 | |
| 512 | 513 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 6 |
| 513 | 514 | InputRegister | U16 | h | Running hours – Electric heater 2, section 6 | |
| 514 | 515 | InputRegister | U16 | Start count – Electric heater 2, section 6 | ||
| 515 | 516 | InputRegister | U16 | see Register states | State – Electric heater 2, section 7 | |
| 516 | 517 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 7 |
| 517 | 518 | InputRegister | U16 | h | Running hours – Electric heater 2, section 7 | |
| 518 | 519 | InputRegister | U16 | Start count – Electric heater 2, section 7 | ||
| 519 | 520 | InputRegister | U16 | see Register states | State – Electric heater 2, section 8 | |
| 520 | 521 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 8 |
| 521 | 522 | InputRegister | U16 | h | Running hours – Electric heater 2, section 8 | |
| 522 | 523 | InputRegister | U16 | Start count – Electric heater 2, section 8 | ||
| 523 | 524 | InputRegister | U16 | see Register states | State – Electric heater 2, section 9 | |
| 524 | 525 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 9 |
| 525 | 526 | InputRegister | U16 | h | Running hours – Electric heater 2, section 9 | |
| 526 | 527 | InputRegister | U16 | Start count – Electric heater 2, section 9 | ||
| 527 | 528 | InputRegister | U16 | see Register states | State – Electric heater 2, section 10 | |
| 528 | 529 | InputRegister | U16 | % | 0–100 | Output – Electric heater 2, section 10 |
| 529 | 530 | InputRegister | U16 | h | Running hours – Electric heater 2, section 10 | |
| 530 | 531 | InputRegister | U16 | Start count – Electric heater 2, section 10 | ||
| 531 | 532 | InputRegister | U16 | % | 0–100 | Total output – Electric heater 3 |
| 532 | 533 | InputRegister | U16 | see Register states | State – Electric heater 3, section 1 | |
| 533 | 534 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 1 |
| 534 | 535 | InputRegister | U16 | h | Running hours – Electric heater 3, section 1 | |
| 535 | 536 | InputRegister | U16 | Start count – Electric heater 3, section 1 | ||
| 536 | 537 | InputRegister | U16 | see Register states | State – Electric heater 3, section 2 | |
| 537 | 538 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 2 |
| 538 | 539 | InputRegister | U16 | h | Running hours – Electric heater 3, section 2 | |
| 539 | 540 | InputRegister | U16 | Start count – Electric heater 3, section 2 | ||
| 540 | 541 | InputRegister | U16 | see Register states | State – Electric heater 3, section 3 | |
| 541 | 542 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 3 |
| 542 | 543 | InputRegister | U16 | h | Running hours – Electric heater 3, section 3 | |
| 543 | 544 | InputRegister | U16 | Start count – Electric heater 3, section 3 | ||
| 544 | 545 | InputRegister | U16 | see Register states | State – Electric heater 3, section 4 | |
| 545 | 546 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 4 |
| 546 | 547 | InputRegister | U16 | h | Running hours – Electric heater 3, section 4 | |
| 547 | 548 | InputRegister | U16 | Start count – Electric heater 3, section 4 | ||
| 548 | 549 | InputRegister | U16 | see Register states | State – Electric heater 3, section 5 | |
| 549 | 550 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 5 |
| 550 | 551 | InputRegister | U16 | h | Running hours – Electric heater 3, section 5 | |
| 551 | 552 | InputRegister | U16 | Start count – Electric heater 3, section 5 | ||
| 552 | 553 | InputRegister | U16 | see Register states | State – Electric heater 3, section 6 | |
| 553 | 554 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 6 |
| 554 | 555 | InputRegister | U16 | h | Running hours – Electric heater 3, section 6 | |
| 555 | 556 | InputRegister | U16 | Start count – Electric heater 3, section 6 | ||
| 556 | 557 | InputRegister | U16 | see Register states | State – Electric heater 3, section 7 | |
| 557 | 558 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 7 |
| 558 | 559 | InputRegister | U16 | h | Running hours – Electric heater 3, section 7 | |
| 559 | 560 | InputRegister | U16 | Start count – Electric heater 3, section 7 | ||
| 560 | 561 | InputRegister | U16 | see Register states | State – Electric heater 3, section 8 | |
| 561 | 562 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 8 |
| 562 | 563 | InputRegister | U16 | h | Running hours – Electric heater 3, section 8 | |
| 563 | 564 | InputRegister | U16 | Start count – Electric heater 3, section 8 | ||
| 564 | 565 | InputRegister | U16 | see Register states | State – Electric heater 3, section 9 | |
| 565 | 566 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 9 |
| 566 | 567 | InputRegister | U16 | h | Running hours – Electric heater 3, section 9 | |
| 567 | 568 | InputRegister | U16 | Start count – Electric heater 3, section 9 | ||
| 568 | 569 | InputRegister | U16 | see Register states | State – Electric heater 3, section 10 | |
| 569 | 570 | InputRegister | U16 | % | 0–100 | Output – Electric heater 3, section 10 |
| 570 | 571 | InputRegister | U16 | h | Running hours – Electric heater 3, section 10 | |
| 571 | 572 | InputRegister | U16 | Start count – Electric heater 3, section 10 | ||
| 599 | 600 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Defrost 5 = Fault 6 = Delay 7 = Defrost - frost protection 8 = Manual – waiting for airflow 9 = PEC100 fault |
State – Integrated heat pump 1 | |
| 600 | 601 | InputRegister | U16 | % | 0–100 | Axial fan speed – Heat pump 1 |
| 601 | 602 | InputRegister | U16 | see Register states | Compressor 1 state – Heat pump 1 | |
| 602 | 603 | InputRegister | U16 | 0 = Off 1 = Running |
Compressor 1 running – Heat pump 1 | |
| 603 | 604 | InputRegister | U16 | % | 0–100 | Compressor 1 output – Heat pump 1 |
| 604 | 605 | InputRegister | U16 | h | Running hours compressor 1 – Heat pump 1 | |
| 605 | 606 | InputRegister | U16 | Start count compressor 1 – Heat pump 1 | ||
| 606 | 607 | InputRegister | U16 | see Register states | Compressor 2 state – Heat pump 1 | |
| 607 | 608 | InputRegister | U16 | 0 = Off 1 = Running |
Compressor 2 running – Heat pump 1 | |
| 608 | 609 | InputRegister | U16 | % | 0–100 | Compressor 2 output – Heat pump 1 |
| 609 | 610 | InputRegister | U16 | h | Running hours compressor 2 – Heat pump 1 | |
| 610 | 611 | InputRegister | U16 | Start count compressor 2 – Heat pump 1 | ||
| 611 | 612 | InputRegister | U16 | 0 = Off 1 = Heating 2 = Cooling 3 = Manual control 4 = Defrost 5 = Fault 6 = Delay 7 = Defrost - frost protection 8 = Manual – waiting for airflow 9 = PEC100 fault |
State – Integrated heat pump 2 | |
| 612 | 613 | InputRegister | U16 | % | 0–100 | Axial fan speed – Heat pump 2 |
| 613 | 614 | InputRegister | U16 | see Register states | Compressor 3 state – Heat pump 2 | |
| 614 | 615 | InputRegister | U16 | 0 = Off 1 = Running |
Compressor 3 running – Heat pump 2 | |
| 615 | 616 | InputRegister | U16 | % | 0–100 | Compressor 3 output – Heat pump 2 |
| 616 | 617 | InputRegister | U16 | h | Running hours compressor 3 – Heat pump 2 | |
| 617 | 618 | InputRegister | U16 | Start count compressor 3 – Heat pump 2 | ||
| 618 | 619 | InputRegister | U16 | see Register states | Compressor 4 state – Heat pump 2 | |
| 619 | 620 | InputRegister | U16 | 0 = Off 1 = Running |
Compressor 4 running – Heat pump 2 | |
| 620 | 621 | InputRegister | U16 | % | 0–100 | Compressor 4 output – Heat pump 2 |
| 621 | 622 | InputRegister | U16 | h | Running hours compressor 4 – Heat pump 2 | |
| 622 | 623 | InputRegister | U16 | Start count compressor 4 – Heat pump 2 | ||
| 649 | 650 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Supply filter 1 | |
| 650 | 651 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Supply filter 1 (0 when there is no second stage) | |
| 651 | 652 | InputRegister | U16 | Pa | Stage 1 pressure difference – Supply filter 1 (0 without analog sensor) | |
| 652 | 653 | InputRegister | U16 | Pa | Stage 2 pressure difference – Supply filter 1 (0 without analog sensor or second stage) | |
| 653 | 654 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Supply filter 2 | |
| 654 | 655 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Supply filter 2 (0 when there is no second stage) | |
| 655 | 656 | InputRegister | U16 | Pa | Stage 1 pressure difference – Supply filter 2 (0 without analog sensor) | |
| 656 | 657 | InputRegister | U16 | Pa | Stage 2 pressure difference – Supply filter 2 (0 without analog sensor or second stage) | |
| 657 | 658 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Supply filter 3 | |
| 658 | 659 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Supply filter 3 (0 when there is no second stage) | |
| 659 | 660 | InputRegister | U16 | Pa | Stage 1 pressure difference – Supply filter 3 (0 without analog sensor) | |
| 660 | 661 | InputRegister | U16 | Pa | Stage 2 pressure difference – Supply filter 3 (0 without analog sensor or second stage) | |
| 661 | 662 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Exhaust filter 1 | |
| 662 | 663 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Exhaust filter 1 (0 when there is no second stage) | |
| 663 | 664 | InputRegister | U16 | Pa | Stage 1 pressure difference – Exhaust filter 1 (0 without analog sensor) | |
| 664 | 665 | InputRegister | U16 | Pa | Stage 2 pressure difference – Exhaust filter 1 (0 without analog sensor or second stage) | |
| 665 | 666 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Exhaust filter 2 | |
| 666 | 667 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Exhaust filter 2 (0 when there is no second stage) | |
| 667 | 668 | InputRegister | U16 | Pa | Stage 1 pressure difference – Exhaust filter 2 (0 without analog sensor) | |
| 668 | 669 | InputRegister | U16 | Pa | Stage 2 pressure difference – Exhaust filter 2 (0 without analog sensor or second stage) | |
| 669 | 670 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 1 state – Exhaust filter 3 | |
| 670 | 671 | InputRegister | U16 | 0 = OK 1 = Dirty 2 = Clogged |
Stage 2 state – Exhaust filter 3 (0 when there is no second stage) | |
| 671 | 672 | InputRegister | U16 | Pa | Stage 1 pressure difference – Exhaust filter 3 (0 without analog sensor) | |
| 672 | 673 | InputRegister | U16 | Pa | Stage 2 pressure difference – Exhaust filter 3 (0 without analog sensor or second stage) |