The CLIMAN controller acts as the Modbus master towards the components and room devices. This page lists the Modbus address and the communication parameters the unit expects from each component – the component must be set to these values, otherwise the controller will not establish communication with it.
For the opposite direction – the register map where CLIMAN acts as the Modbus slave towards the supervisory system (BMS/SCADA) – see the Modbus table page.
The controller's serial Modbus lines (RS-485) use the default settings:
| Parameter | Value |
|---|---|
| Baud rate | 19200 bps |
| Data bits | 8 |
| Parity | Even |
| Stop bits | 1 |
The controller has two RS-485 serial lines:
| Component | Manufacturer / model | Address(es) | Bus |
|---|---|---|---|
| Expansion modules | CLIMAN (EK) | 1–30 | RS-485 no. 1 |
| EC fans | EBM-PAPST | 61–80 | RS-485 no. 1 |
| EC fans | ZIEHL-ABEGG ECblue | 101–120 | RS-485 no. 1 |
| Frequency inverters | Danfoss | 201–202 | RS-485 no. 1 |
| Electronic expansion valve driver | CAREL EVD evolution | 51–52 | RS-485 no. 1 |
| Compressor controller | Copeland OUC | 31–32 | RS-485 no. 1 |
| Compressor controller | Emerson PECC100 | 41–42 | RS-485 no. 1 |
| Room controller | Belimo P-22RTH-1U00D-2 | 1 | RS-485 no. 2 |
No two devices on the same serial line may share an address. The ranges above are chosen so that they do not overlap on one line; room devices (Belimo, address 1) are therefore on a separate RS-485 line no. 2. Addresses 1–30 on RS-485 no. 1 are reserved for the CLIMAN (EK) expansion modules, so external devices on this line start from address 31.
RS-485 bus wiring guidelines
- Cable: shielded twisted pair for data buses – the A/B data pair in one twist, with shield. We recommend a multi-pair cable (spare pair for future use). Example: J-Y(St)Y 2×2×0.8 (or 3×2×0.8), or an equivalent – shielded CAT 5E or a dedicated RS-485/Modbus cable, 120 Ω.
- Topology: daisy-chain. Not a star; stub max 1 m.
- Termination: 120 Ω resistor only at the two ends of the bus (not in the middle). At the last device via the END switch; intermediate devices END = OFF.
- Consistent parameters: default baud rate 19200 bps; baud rate and parity must be the same on all devices on the branch.
- Length: the higher the baud rate, the shorter the maximum length (RS-485 standard up to 1200 m / 31 devices per branch at low speed).
- Polarity: keep A↔A, B↔B on all devices.
- Shield: bond and earth it at a single point only (usually at the controller).
- Routing: route the data bus separately from power cables.
Wiring diagrams (correct / common mistakes) are in the RS-485 installation sheet (PDF).