¶ Modbus – register states, Mandík AHU (Climan)
Supplement to the Modbus table. Only the state enumerations that are
too long to fit into the register table are listed here. Shorter enumerations are directly in the table.
Alarm numbers have their own page Alarm numbers.
Values not listed should not occur in the given register. If one appears, the unit runs a newer
application version than this document was written for – ignore the value.
| Code |
Description |
| 0 |
Off |
| 1 |
Qualitative ventilation |
| 2 |
Qualitative heating |
| 3 |
Quantitative heating |
| 4 |
Qualitative cooling |
| 5 |
Quantitative cooling |
| 6 |
Quantitative ventilation |
| 7 |
Pre-purge |
| 8 |
Cooling cascade not configured |
| 9 |
Heating cascade not configured |
| 10 |
AHU is without cooling |
| 11 |
AHU is without heating |
| 12 |
Maximum supply temperature |
| 13 |
Minimum supply temperature |
| 14 |
Ventilation with controlled recuperation |
| 15 |
Ventilation with controlled mixing |
| 16 |
Cooling disabled |
| 17 |
Heating disabled |
| 18 |
Post-heating delay |
| 19 |
Post-cooling delay |
| 20 |
Cooling locked by outdoor temp |
| 21 |
Heating locked by outdoor temp |
| 22 |
Night free cooling |
| 44 |
Post-ventilation |
| 45 |
Dehumidification |
| 50 |
Heating at maximum |
| 51 |
Quantitative heating at max |
| 52 |
Max airflow – heating |
| 53 |
Cooling at maximum |
| 54 |
Quantitative cooling at max |
| 55 |
Max airflow – cooling |
| 60 |
Switching to quant. ventilation |
| 61 |
Switching to cooling |
| 62 |
Switching to heating |
| 63 |
Heating → ventilation |
| 64 |
Heating qual. → quant. |
| 65 |
Heating quant. → qual. |
| 66 |
Cooling → ventilation |
| 67 |
Cooling qual. → quant. |
| 68 |
Cooling quant. → qual. |
| 69 |
Quant. ventilation → cooling |
| 70 |
Quant. ventilation → qual. |
| Code |
Description |
| 0 |
Off |
| 1 |
Qualitative ventilation |
| 2 |
Humidification |
| 3 |
Quantitative humidification |
| 4 |
Dehumidification |
| 5 |
Dehumidification – reduced airflow |
| 6 |
Quantitative ventilation |
| 7 |
Switching to dehumidification |
| 8 |
Switching to humidification |
| 9 |
Dehumidification disabled |
| 10 |
Cooler for dehumidification missing |
| 11 |
Lockout after humidification |
| 12 |
Humidification disabled |
| 13 |
Humidifier not installed |
| 14 |
Lockout after dehumidification |
| 15 |
Switching to dehumidification by ventilation |
| 16 |
Switching to humidification by ventilation |
| 17 |
Reheat missing |
| 18 |
Dehumidification – reheat at limit |
| 19 |
Dehumidification cascade not set |
| 20 |
Reheat cascade not set |
Says what is currently determining the fan speed.
| Code |
Description |
| 0 |
Waiting for dampers |
| 1 |
Controlled by temperature manager |
| 2 |
Controlled by air quality |
| 3 |
Controlled by humidity manager |
| 4 |
Stopped due to alarm |
| 5 |
Speed adjusted by room device |
| 6 |
Externally controlled |
| 7 |
Heat pump run-on |
| 8 |
Condenser unit defrost |
| 9 |
Module post-ventilation |
| 10 |
Manual fan operation |
| 11 |
Water heater frost protection |
| 12 |
Night free cooling |
| 13 |
Zones |
| 14 |
Zones closed |
Applies to the state of every section of all condensing units.
| Code |
Description |
| 0 |
Off |
| 1 |
Heating |
| 2 |
Cooling |
| 3 |
Manual control |
| 4 |
Defrost |
| 5 |
Fault |
| 6 |
Manual – waiting for airflow |
| 7 |
Delay |
Applies to the state of every section of all electric heaters.
| Code |
Description |
| 0 |
Off |
| 1 |
Auto |
| 2 |
Max |
| 3 |
Manual control |
| 4 |
Fault |
| 5 |
Overheat |
| 6 |
Reheat during dehumidification |
The meaning depends on the type of integrated heat pump. Which enumeration applies is given by the
unit's equipment – you can find it on the unit's web server; the type is not transmitted over Modbus.
¶ Standard heat pump
| Code |
Description |
| 0 |
Disabled |
| 1 |
Alarm |
| 2 |
Startable |
| 3 |
Starting |
| 4 |
Started |
| 5 |
Stoppable |
| 6 |
Stopping |
| 7 |
Stopped |
| Code |
Description |
| 0 |
Off |
| 1 |
Cooling |
| 2 |
Heating |
| 3 |
Alarm |
| 4 |
Transition to defrost |
| 5 |
Defrost |
| 6 |
Waiting |
| 7 |
Standby |
| 8 |
Transition to heating |
| 9 |
Stopping |
| 10 |
Manual |
| 11 |
Compressor start |
| 12 |
EVU lock |
| 13 |
Pre opening (N/A) |
| 14 |
Press. equal. |
| 15 |
Evacuation |
| 16 |
Diagnosis |
| 17 |
Diagnosis |